S-CB
+
Boiler Range Manual
33
8.9.3
E
XAMPLE
C:
S
INGLE FLUE GAS OUTLET
.
A
IR SUPPLY FROM BOILER ROOM
100
4
m
2m
3
m
2m
2
m
Boiler type:
S-CB
+
100
Flue gas
Diameter: 100 mm
Number
Pa
Pa total
Straight tube m¹
total
13
4
52
Bend
90°
2
4
8
Bend
45°
2
2
4
Flue outlet
H/D = 1,0
1
15,2
15,2
Total resistance flue gas outlet:
79,2
Calculation example with given lengths: checking resistance
The total resistance is less than 200 Pa. This flue gas / air supply system is
functional.
Summary of Contents for S-CB+ Series
Page 2: ......
Page 3: ......
Page 22: ...S CB Boiler Range Manual 22 ...
Page 39: ...S CB Boiler Range Manual 39 9 4Electrical schematics ...
Page 124: ...S CB Boiler Range Manual 124 ...