S-CB
+
Boiler Range Manual
11
Type boiler
S-CB
+
60
S-CB
+
80 S-CB
+
100 S-CB
+
120 S-CB
+
150 S-CB
+
180
EMISSION
[EN437]
Values min-max:
CO
2
flue gas
3
G25/G20
%
8,7 - 9,0 8,7 - 9,0 8,7 - 9,0 8,7 - 9,0 8,7 - 9,0 8.7 - 9.0
G31
%
9,3 - 10,3 9,3 - 10,3 9,3 - 10,3 9,3 - 10,3 9,3 - 10,4 9.3 - 10.5
G30 (B/P)
%
9,3 - 10,4 9,3 - 10,4 9,3 - 10,4 9,3 - 10,4 9,3 - 10,5 9.3 - 10.6
NOx at 0% O
2
, year emission
ppm
21,0
31,5
24,6
27,4
25,3
16,5
mg/kWh
37,7
56,6
44,2
49,2
45,4
29,7
NOx class [EN483 / EN15420]
-
5
Flue gas temperature at combustion
air temperature = 20°C
°C
~ 85-95
Available pressure for the flue sys-
tem
4
Pa
200
INSTALLATION
Available pressure for
the installation at
T = 20 K
mWC
3,8
1,3
1,5
1,0
0,7
0,1
T = 25 K
mWC
5,1
3,7
3,7
3,0
3,2
2,5
Pressure boiler min-max.
bar
1,0 - 4,0
5
Max. flow temperature
°C
90
ELECTRIC
Power consumption
W
355
355
355
370
600
Power supply
V/Hz
230/50
Protection class
-
IPX4D
NOTES
3
CO
2
of the unit measured/set without the boiler
front panel in place
4
Maximum allowed combined resistance of flue
gas and air supply piping at high fire
5
When the built-in water pressure sensor is replaced
by a water pressure switch,
water pressure may go
up to 6,0 bar