S-CB
+
Boiler Range Manual
10
2.2 Technical specifications datasheet
GENERAL
Product Identification Number
-
CE 0063 BP3254
Classification
-
II2H3P (for NL II2L3P)
Gas Appliance Type
-
B23, B23P; C13X, C23X, C33X, C43X, C53X, C63X, C83X
Type boiler
S-CB
+
60
S-CB
+
80
S-CB
+
100 S-CB
+
120 S-CB
+
150 S-CB
+
180
Dimensions (h x w x d)
mm
842 x 476 x 486
898 x 476 x 677
Water content estimated
litre
3,9
5,0
6,5
8,3
10,4
12,9
Weight (empty)
kg
46
73
78
83
92
101
Flow/return connection (boiler)
inch
R 1”
R 1”
R 1”
R 1”
R 1¼”
R 1¼”
Flow/return connection (T-piece)
inch
Rp 1¼”
Rp1¼”
Rp 1¼”
Rp 1¼”
Rp 1½”
Rp 1½”
Gas connection
inch
R ¾”
R ¾”
R ¾”
R ¾”
R 1”
R 1”
Flue duct flue/air inlet (* as supplied) mm
80/125
*
80/125
*
100/150
*
100/150
*
100/150
100/150
Parallel connection (* as supplied)
mm
80-80
80-80
100-100
100-100
130-130
*
130-130
*
HEATING
Values min-max:
Nominal input (Net)
kW
12,5 - 55,6 14,6 - 74,3 17,2 - 92,2 26,0 - 111 34,0 - 138 45,0 - 166
Nominal input (gross) (G20, G25)
kW
13,9 - 61,8 16,2 - 82,5 19,1 - 102 28,9 - 123 37,8 - 153 50,0 - 184
Nominal input (gross) (G31)
kW
13,6 - 60,4 15,9 - 80,8 18,7 - 100 28,3 - 121 37,0 - 150 48,9 - 180
Nominal input (gross) (G30)
kW
13,5 - 60,3 15,8 - 80,2 18,6 - 99,7 34,7 - 120 36,8 - 150 48,8 - 180
Nom. output 80/60°C
kW
12,0 - 53,5 14,0 - 71,2 16,5 - 88,4 24,7 - 106 32,6 - 132 43,3 - 160
Nom. output 50/30°C
kW
12,9 - 57,4 15,2 - 77,5 18,0 - 96,2 27,2 - 116 35,5 - 144 47,3 - 175
Nom. output 37/30°C
kW
13,5 - 59,8 15,7 - 80,1 18,6 - 99,5 28,1 - 120 36,7 - 149 48,5 - 179
Efficiency 40/30°C DIN 4702-8
%
up to 110,6 % within the S-CB
+
range
GAS CONSUMPTION
[EN437]
Values min-max:
Natural gas
G25
m³
st
/h
1,54 - 6,84 1,80 - 9,14 2,12 - 11,4 3,20 - 13,7 4,18 - 17,0 5,54 - 20,4
Natural gas
G20
m³
st
/h
1,32 - 5,88 1,54 - 7,86 1,82 - 9,76 2,75 - 11,8 3,60 - 14,6 4,76 - 17,6
Propane gas G31
1
m³
st
/h
0,51 - 2,27 0,60 - 3,04 0,70 - 3,77 1,06 - 4,54 1,39 - 5,65 1,84 - 6,79
Butane gas
(B/P) G30
1
m³
st
/h
0,39 - 1,72 0,45 - 2,29 0,53 - 2,85 0,99 - 3,44 1,05 - 4,28 1,40 - 5,15
Gas supply pressure
nom.
2
G25
mbar
25
G20
mbar
20
G31
1
mbar
30/37
G30
1
mbar
50
NOTES
1
Using propane or butane/propane mixtures (B/P), maximum fan speed needs to be reduced (parameter P4BD)
2
Min. and max. gas supply pressures according to EN437:
p nominal [mbar]
p min [mbar]
p max [mbar]
G25
25
20
30
G20
20
17
25
G31
30
25
35
37
25
45
G30
50
43
57
Summary of Contents for S-CB+ Series
Page 2: ......
Page 3: ......
Page 22: ...S CB Boiler Range Manual 22 ...
Page 39: ...S CB Boiler Range Manual 39 9 4Electrical schematics ...
Page 124: ...S CB Boiler Range Manual 124 ...