5-16
122998-741
Operator Manual
Cycle and Control Value Programming
5.7.2 Prior to Starting a Cycle
1.
Once cycle is selected, press
REVIEW CYCLE
touch pad to
access Cycle Review mode. Continue to press
REVIEW CYCLE
to advance screen to desired phase.
CYCLE 6
SP=180.0F
RINSE 1
T=1:30
2.
With correct cycle phase displayed, press
EXTEND CYCLE
touch pad. Programmed phase time is temporarily doubled. If
EXTEND CYCLE
is pressed again, phase time returns to original
programmed time set point.
CYCLE 6
SP=180.0F
RINSE 1
ET=3:00
NOTE: While in Cycle Review mode, EXTEND CYCLE touch pad
only allows operator to double programmed phase time. If a
longer phase time is desired, programmed time set point must
either be manually extended during cycle or adjusted in Change
Values mode prior to starting cycle.
3.
Press
REVIEW CYCLE
touch pad until print message appears
on screen.
PRINT CYCLE VALUES?
REVIEW = YES
STOP = NO
NOTE: To run cycle with extended phase times, cycle must be
started while in Cycle Review mode. To remain in Cycle Review
mode, operator must answer YES to print message by pressing
REVIEW CYCLE touch pad. If operator answers NO by pressing
Stop/Reset, control exits Cycle Review mode, display screen
returns to cycle menu, and any adjustments made while in Cycle
Review mode are erased.
4.
Press
REVIEW CYCLE
touch pad to generate a printout of
reviewed cycle values and return display screen to first phase of
selected cycle. An "X" will be printed next to each extended
phase time.
======================
CYCLE PROGRAM REVIEW
= CYCLE - CYCLE 6 =
======================
REVIEW TIME
5:18:25P
REVIEW DATE
4/24/92
UNIT NUMBER
0000000
PHASE
TIME
F
---------------------------------------------
PRE-WASH 1:00
HTW
DET-WASH 5:00
140.0
RINSE 1 E 3:00
180.0
RINSE 2
1:30
180.0
F. RINSE
1:30
180.0G
EXHAUST 1:30
-----
----------------------------------------------