Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications
97
Example:
Output value (
°
C)
100
0,5
0
2
4
6
8
10
An input range of 0...10 V is actual. Values between 2 and 8 V are to be screened upon 0.5…100 °C as shown above.
Additionally to the four curve points (•) the smallest and the largest possible value (x) must be specified. In the present
example the input values 0 V and 2 V equal output values are assigned to. The same applies to the input values 8 V and 10 V.
To define the pictured linearization curve, therefore, six pairs of values are required.
The range configured for the appurtenant actual value (see CONFIGURATION Actual Values) is only relevant for a contingent
DAC output.
Input value (V)