Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
150
Subject to technical modifications
The C-level calculation uses analogue variables (numeric) for input and output values. It concerns a memory area which can
optionally be divided to integer (16), integer (32), or real variables. These variables can be displayed and inputted at the
device; furthermore, the control system can read and write the variables.
Configuration of the C-level variables:
The C-level calculation needs six variables per C-level:
Variable 1 C-level in %
Variable 2 CO value in %
Designation
C-level
Designation text
CO actual value
Dimension text
%
Dimension text
% CO
Variable type
IEEE-Float
Variable type
IEEE-Float
Display format
##0.00
Display format
##0.0
Float lower limit
0.00
Float lower limit
4.0
Float upper limit
1.60
Float upper limit
35.0
Control system address
4500
Control system address
4502
Initialization mode
None
Initialization mode
None
Variable 3 O
2
probe in mV
Variable 4 Temperature in °C
Designation text
Oxygen
Designation text
Temperature
Dimension text
mV
Dimension text
°C
Variable type
IEEE-Float
Variable type
IEEE-Float
Display format
##0
Display format
##0
Float lower limit
1000
Float lower limit
700
Float upper limit
1300
Float upper limit
1100
Control system address
4504
Control system address
4506
Initialization mode
None
Initialization mode
None
Variable 5 Correction factor
Variable 6 CO
2
-value in % CO
2
Designation text
Correction factor
Designation text
CO
2
actual value
Dimension text
-
Dimension text
% CO
2
Variable type
IEEE-Float
Variable type
IEEE-Float
Display format
##0.0
Display format
##0.00
Float lower limit
0.8
Float lower limit
0.01
Float upper limit
1.2
Float upper limit
1.00
Control system address
4508
Control system address
4510
Initialization mode
None
Initialization mode
None