Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications
87
8.3.3.2 Actual values
Overview of the actual values:
- Actual value No.
- Description
- Type
- Dimension
Functions are defined by operating the “Edit” button.
The numbers of parameters are defined by operating the
“PARAM” button.
Functions for each actual value:
Function
Input Range
Parameter:
Number
Number of actual values
Description
Actual value name, max. 24 characters
Linearization type
Max. range °C
Max. range °F
Unassigned
-9999..+9999
-9999..+9999
Linear
2
-9999..+9999
-9999..+9999
Fe / CuNi (constantan), DIN 43710
-200..+900
-328..+1652
Fe / CuNi (constantan), Type J
-200..+1200
-328..+2192
Pt100, 4-wire
-200..+850
-328..+1652
Nicrosil / Nisil, IEC 584 , NiCrSi-NiSi Type N
-260..+1300
-436..+2372
NiCr / Ni, Type K
-200..+1400
-328..+2552
Ni / NiMo18%
0..+1400
+32..+2552
Pt / PtRh10%, Type S
0..+1800
+32..+3272
Pt / PtRh13%, Type R
-50..+1769
-58..+3216
WRe5% / WRe26%
0..+2320
+32..+4208
WRe3% / WRe25%
0..+2400
+32..+4352
PtRh30% / PtRh6%, EL18, Type B
0..+1820
+32..+3308
Pt100, 3-wire
-200..+850
-328..+1562
Cu / CuNi (constantan), Type T
-270..+400
-454..+752
Pt20%Rh/Pt40%Rh
0..+1888
+32..+3430
Ir40%Rh/Ir
0..+2003
+32..+4177
Free linearization curve 1
3
-9999..+9999
-9999.+9999
Free linearization curve 2
3
-9999..+9999
-9999.+9999
Range code
Input range in case of linear signal: 0...10 Volt, 0...20 mA, 4... 0 mA
Actual value function
None, °C in °F convert, actual value scaling
1
, actual value scaling with limit.
1
Display format
Actual value display format according to format enumeration
Low range limit
Input range: -9.99999E15 to +9.99999E15
High range limit
Input range -9.99999E15 to +9.99999E15
Dimension text
Max. 10 characters
Mean value number
0...50
Number of correction points
0...5
Actual value correction point 1-5
5 actual value correction points, general input range: -9.99999E15 to +9.99999E15,
Actual value range is considered in addition
Correction point 1-5
5 actual value correction points, general input range: -9.99999E15 to +9.99999E15,
Actual value range is considered in addition (correction value m/- 10% from
actual value range)
Error message
Sensor break/Ufl./Ofl.
Actual value at sensor break/Ufl./Ofl.
Value from actual value processing, range upper limit, range lower limit, fixed value
Measuring rate CAN basis linear
Standard, high speed
Actual value factor
Range: -9.99999E15 to +9.99999E15
Actual value offset
Range: -9.99999E15 to +9.99999E15
Number of filter values
0…9
Number of sequenced values which are ignored if they are located in the “filter
window”
Filter window
00,01…99,99 % (related to actual value range)