Measuring rate for linear actual values on the CAN-Basis (not applicable for SIOS)
- If CAN modules for fast actual value processing are used for standard signals (CAN-IW8-Q) with the remote
peripherals, then the measuring speed for each there configured actual value can be determined (normal or fast).
The measuring rate for the CAN-IW8-QB amounts in normal operation 950 ms, for fast operation 95 ms.
- If CAN modules for thermocouple and standard signals (CAN-IW4-XL and CAN-IW8-XL) are used with the remote
peripherals, then one standard signal actual value per input module can be measured favoured (faster). The
measuring rate for fast operation amounts 400 ms for an IWx-XL module.
ATTENTION!
Only one standard signal channel per module may be configured ”fast” in case of using CAN-IW4-XL and CAN-IW8-
XL modules. If several actual values are configured “fast” for these modules by mistake, then only the last actual
value of the corresponding module is measured favoured.
Thermocouples cannot be measured favoured.