Program Controller SE-707
© 2018 by STANGE Elektronik GmbH
Subject to technical modifications
159
Data logger-configuration (changeable settings during plant project planning)
Logger-Parameter
Menu:
→
Configuration
→ Special Functions → Data Logger → Parameter (left sidebar)
The parameters are set by selecting the desired parameter and
operating the “Edit” button.
Criteria for the data logger parameters:
Data naming in the device
Description, value range
Head data count
Number of header data fields; Range: 0 to 20
Number of log values
Number of log values; Range: 0 to 32
Logger Mode
The logger mode defines the mode of operation of the data logger:
Disabled
Log data
Alarm logging
Data and alarm logging
Logger Start
The parameter „Logger Start“ defines whether internally or externally can be started:
1= Start only via local operation
2= Start only via external control (FI-967)
3= Start alternatively via local operation or external control (FI-967)
Cycle time 1
Cycle time 1 for data recording, is active if FI964 = 0 and FI965 is = 1;
Value range: 1..9999 seconds
Cycle time 2
Cycle time 2 1 for data recording, is active if FI964 = 1 and FI965 is = 1;
Value range: 1..9999 seconds
Delete: Logfiles storage limit
Limit value log data storage from which is tried to delete (10.0% to 90.0%)
Note: The relation to parameter “Alarm limit log data storage” is to be considered!
Delete: Logfiles count limit
Number of listed LogFiles in directory from which is tried to delete (Range: 20..198)
The relation to parameter “Alarm limit number of log files” is to be considered!
Batch info: Edit before batch start
Batch description, editing before batch start: Yes, No or required
Batch-Info: Edit allowed while batch is
running
Batch description, editing while batch is running: Yes or No
Batch-Info: Edit allowed after batch end
Batch description, editing after batch end: Yes or No
Header data: Edit before batch start
Batch header data, editing before batch start: No, Yes or required
Header data: Edit allowed while batch is
running
Header data, editing while batch is running: Yes or No
Header data: Edit allowed after batch end
Header data, editing after batch end: Yes or No
Comment: Edit before batch start
Batch comment, editing before batch start: No, Yes or required
Comment: Edit allowed while batch is
running
Comment, editing while batch is running: Yes or No
Comment: Edit allowed after batch end
Comment, editing after batch end: Yes or No
Delete mode
Automatic deletion mode:
- Inactive, no automatic deletion of log files
- Delete archived log files corresponding to deletion criteria
- Delete archived log files immediately
- Delete log files corresponding to deletion criteria
Alarm limit log files storage
The alarm limit log data storage, range 50.0% to 95.0%: If this value is exceed, then comes