Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
21
PROFIBUS DP interface for IS1+
2.10 CPU redundancy
Attention!
Two different solutions for CPU redundancy with PROFIBUS DP are available:
CPU redundancy according to PNO specification ´Slave Redundancy´
Doc. 2.212 R1.2 2004
CPM redundancy according to R.STAHL specification
is a proprietary solution from 2000.
IS1 supports both solutions. The two solutions are
not
compatible with one another and must be projected
differently. Therefore, a clear distinction must be made as to which version is to be used.
Selection for the 9442 CPU via the backplane switch S1:
S1 = 1
PROFIBUS PNO Redundancy.
(recommended for new projects)
S1 = 2
PROFIBUS Stahl Redundancy Addr. Offs. 1
S1 = 3
PROFIBUS Stahl Redundancy Addr. Offs. 0
The distinction between STAHL and PNO redundancy for the 9440 CPM is done by selecting the CPM
firmware and the associated GSE file:
*1) Attention!
When using GSE files from V3.03 in connection with IS1 9440 firmware up to V0x-41, a
parameterization error is reported when IS1 is started, if the PLC supports structured parameterization
according to DPV1 (e.g. S7-300 and S7-400). In this case, IS1 will not enter Data_Exchange.
Remedy: use firmware from V0x-42 or GSE up to 3.02.
A maximum of 15 IO-Modules
with IS1+ GSE
from V3.03
A mix of redundant CPMs with firmware acc. R.STAHL spec. and PNO spec. is not allowed in one IS1 field
station. Rule for redundant operation of two IS1 CPMs: Firmware from the same row (01-xx or 02-xx or 03-xx
or 09-xx) shall be used in both CPMs.
-
CPM 9440 redundancy
Usage
STAHL
CPM redundancy according Stahl specification
PNO
CPM redundancy according to PNO specification
GSE
GSE V2.xx
DPV0 diagnosis
from PROFIBUS firmware version V0x-30
from
GSE V2.25
for masters
non
-
compliant with
PNO slave
redundancy
Standard solution
for new projects
GSE from V3.03
DPV1 diagnosis
with status and structured
parameterization
*1)
from PROFIBUS firmware version V0x-42
(GSE V3.00 to V3.02 from PROFIBUS
firmware version V0x-40)
from
GSE V3.03
for masters
compliant with
PNO slave
redundancy
(max. 15 IO-
Module!)
New projects
with DPV1 compatible
DP Masters
and for use with
PROFIsafe
e.g. S7-400H, S7-300F, S7-
400F …
IS1 CPM
Firmware
V01-42
-
DPV0 Version
without C2 communication
V02-42
from V03-42
DPV1 Version
(with C2 communication, HART,
DTM support, I&M, …)
V09-42
-
DPV1 Version
(as above, but
Offset backup addr. = 0 )