Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
48
PROFIBUS DP interface for IS1+
3.2.3.6 TIM 9482
Parameter
Default value
Value range / selection
Diagnostic messages of the module
On
Off
On
Module operation mode
8 channel precise
8 channel precise
4 channel fast
Signal in case of error I 0
Status code
Status code
freeze (initialization value 0%)
Signal in case of error I 1
Status code
. . .
. . .
Signal in case of error I 6
Status code
Signal in case of error I 7
Status code
Error detection I 0
On
Off
On
Error detection I 1
On
. . .
. . .
Error detection I 6
On
Error detection I 7
On
Selection TC cold junction
Internal
Internal
External 3 wire
Type TC ext. cold junction I6-I7
PT100
PT100
PT1000
PT100 GOST
Type I 0
PT100
Pt100
Pt500
Pt1000
Ni100
Ni500
Ni1000
Resistance (Pot) 10k
Resistance (Pot) 5k
Resistance (Pot) 2k5
Resistance (Pot) 500R
Pt100 GOST
M50 GOST
M100 GOST
Cu53 GOST
Pt46 GOST
Pt50 GOST
0…100 mV
THC Type B
THC Type E
THC Type J
THC Type K
THC Type N
THC Type R
THC Type S
THC Type T
THC Type L
THC Type U
THC Type XK (L)
Type I 1
PT100
Type I 2
PT100
Type I 3
PT100
Type I 4
PT100
Type I 5
PT100
Type I 6
PT100
Type I 7
PT100
Connection (R) I 0 *1)
4 wire
measure (R in Ohm)
2 wire measure (Pot in Ohm)
3 wire measure (Pot in %)
4 wire measure (Pot in Ohm)
4 wire
measure (Pot in %)
Connection (R) I 1
4 wire
measure (R in Ohm)
. . .
. . .
Connection (R) I 6
4 wire
measure (R in Ohm)
Connection (R) I 7
4 wire
measure (R in Ohm)
*1) Parameter ´Connection´ using THC not functioning. 2 wire measurement is used for TCH