Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
57
PROFIBUS DP interface for IS1+
3.2.4.5 TIM 9482
Byte
Default [Hex]
7
6
5
4
3
2
1
0
Parameter
Value
0
01
1
Diagnostic messages of the module
0 = Off
1 = On
0
Module operation mode
0 = 8 channel precise
1 = channel fast
0
0
0
0
0
0
Reserviert
1
BB
0
1
1 Signal in case of error I 0
3 = Status Code
6 = freeze (initialization value 0%)
1
Error detection I 0
0 = Off
1 = On
0
1
1
Signal in case of error I 1
1
Error detection I 1
2
BB
I 2 see Byte 1
I 3 see Byte 1
3
BB
I 4 see Byte 1
I 5 see Byte 1
4
BB
0
1
1 Signal in case of error I 6
1
Error detection I 6
0
1
1
Signal in case of error I 7
1
Error detection I 7
5
00
0
Selection TC cold junction
0 = Internal
1 = External 3 wire
0
0
Type TC ext. cold junction I6-I7
0 = PT100
1 = PT1000
2 = PT100 GOST
0
0
Reserviert
0
Reserviert
0
Reserviert
0
Reserviert
6
80
0
0
0
0
0
0 Type I 0
Type :
0 = Pt100
1 = Pt500
2 = Pt1000
3 = Ni100
4 = Ni500
5 = Ni1000
6 = Resistance (Pot)10k
7 = Resistance (Pot) 5k
8 = Resistance (Pot) 2k5
9 = Resistance (Pot) 500R
10 = Pt100 GOST
11 = M50 GOST
12 = M100 GOST
13 = Cu53 GOST
14 = Pt46 GOST
15 = Pt50 GOST
(
16…31 = reserved)
32 = 0…100 mV
33 = THC Type B
34 = THC Type E
35 = THC Type J
36 = THC Type K
37 = THC Type N
38 = THC Type R
39 = THC Type S
40 = THC Type T
41 = THC Type L
42 = THC Type U
43 = THC Type XK(L)
(
44…63 = reserved)
Connection (R): *1)
0 = 2 wire measure (Pot in Ohm)
1 = 3 wire measure (Pot in %)
2 = 4 wire measure (Pot in Ohm)
3 = 4 wire measure (Pot in %)
1
0
Connection (R) I 0
7
80
0
0
0
0
0
0 Type I 1
1
0
Connection (R) I 1
8
80
0
0
0
0
0
0 Type I 2
1
0
Connection (R) I 2
9
80
0
0
0
0
0
0 Type I 3
1
0
Connection (R) I 3
10
80
0
0
0
0
0
0 Type I 4
1
0
Connection (R) I 4
11
80
0
0
0
0
0
0 Type I 5
1
0
Connection (R) I 5
12
80
0
0
0
0
0
0 Type I 6
1
0
Connection (R) I 6
13
80
0
0
0
0
0
0 Type I 7
1
0
Connection (R) I 7
*1) Parameter ´Connection´ using THC not functioning. 2 wire measurement is used for TCH