Channel-related diagnosis
Optionally, additional channel-related diagnosis information in the diagnosis telegram to the master can also
be transmitted. The generation of the channel-related diagnosis can be released in the "USER_PRM_DATA"
area. For each outstanding alarm of the input signals, 3 bytes are transmitted.
Byte
Bit
Value / Info
Message / Function
1
0 - 5
1
– 16
Module slot
6 - 7
0x02
Header
2
0
– 5
0
– 15
Channel / Signal number
6 - 7
00 = reserved
01 = Input
10 = Output
11 = In- / Output
Signal Type
3
0
– 4
0
– 31
Error type - see below
5
– 7
000 = reserved
001 = Bit
010 = 2 Bit
011 = 4 Bit
100 = Byte
101 = word
110 = 2 words
111 = reserved
Data Type
Error
type
Message /
Function
Status Code
in cyclic Data
[Hex]
Measure / Remedy
Signal Status
(NE107)
0
Reserved
-
-
-
-
1
Short circuit
7FFF / 8001
Check connection between IO-Module and
sensor/actuator and remove short.
Check sensor / actuator and replace if required
Failure
2
– 5
Reserved
-
-
-
-
6
Open circuit
7FFA / 8006
Check and reestablish connection between IO-
Module and sensor/actuator.
Check sensor / actuator and replace if required
Failure
7
Upper limit
exceeded
7FF9
Measurement range limit of IO-Module (TIM) is
exceeded.
Use input signal inside allowed measurement range
or choose different range if possible.
8
Lower limit
exceeded
8008
9
– 15
Reserved
-
-
-
-
16
Cold Junction
error
8010
Range of Cold Junction Compensation exceeded.
Check ambient temperature of IO-Module.
Change module
Failure
17
Hardware error
8011
Change module
18
Critical
temperature
8012
Ambient temperature of IO-Module is too high.
Reduce ambient temperature or increase
ventilation, shadowing …
19
2 wire calibration
failed
8013
Repeat 2 wire calibration. Look for a good short at
the wire end during calibration.
20
Parametrization
error
8014
Clear incorrect parameter combination
21
Plant Stop
8015
Check and clear reason for external Plant Stop.
22