Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
58
PROFIBUS DP interface for IS1+
3.2.4.6 DIM (9470/3x in compatible mode)
Byte
Hex
7
6
5
4
3
2
1
0
Parameter
Value
0
01
1
Diagnostic messages of the module
0 = Off
1 = On
0
0
0
0
0
0
0
Not used
1
FF
1
Error detection I 0
0 = Off
1
Error detection I 1
1 = On
1
Error detection I 2
1
Error detection I 3
1
Error detection I 4
1
Error detection I 5
1
Error detection I 6
1
Error detection I 7
2
FF
1
Error detection I 8
1
1
1
1
1
1
...
1
Error detection I 15
3
00
0
0
Signal in case of error I 0
0 = 0
0
0
Signal in case of error I 1
1 = 1
0
0
Signal in case of error I 2
2 = freeze (initial value 0)
0
0
Signal in case of error I 3
3 = freeze (initial value 1)
4
00
0
0
Signal in case of error I 4
0
0
0
0
...
0
0
Signal in case of error I 7
5
00
0
0
Signal in case of error I 8
0
0
0
0
...
0
0
Signal in case of error I 11
6
00
0
0
Signal in case of error I 12
0
0
0
0
...
0
0
Signal in case of error I 15
7
00
0
0
Pulse extension I 0
0 = 0 s
0
0
Pulse extension I 1
1 = 0,6 s
0
0
Pulse extension I 2
2 = 1,2 s
0
0
Pulse extension I 3
3 = 2,4 s
8
00
0
0
Pulse extension I 4
0
0
0
0
...
0
0
Pulse extension I 7
9
00
0
0
Pulse extension I 8
0
0
0
0
...
0
0
Pulse extension I 11
10
00
0
0
Pulse extension I 12
0
0
0
0
...
0
0
Pulse extension I 15
11
00
0
Invert I 0
0 = no
0
Invert I 1
1 = yes
0
Invert I 2
0
Invert I 3
0
Invert I 4
0
Invert I 5
0
Invert I 6
0
Invert I 7
12
00
0
Invert I 8
0
0
0
0
0
0
...
0
Invert I 15
13
11
0
0
1
Operation mode I 14
0 =counter
1 = Freq. 0-1 kHz / DI
2 = Freq. 0-20 kHz gate 50 ms / DI
3 = Freq. 0-20 kHz gate 200 ms / DI
4 = Freq. 0-20 kHz gate 1 s / DI
0
Counter event I 14
0 = Positive edge
1 = Negative edge
0
0
1
Operation mode I 15
s. a.
0