Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
66
PROFIBUS DP interface for IS1+
0 ... 100 mV measurement ( 9481/.., 9482/.. )
Range
0 ... 100 mV
Units
%
Range
Diagnosis messages
decimal
hexadecimal
>117,6 mV
*1)
*1)
Upper limit exceeded
117,6 mV
32511
7EFF
117,6 %
Over range
-
100 mV
27648
6C00
100 %
Nominal range
-
.
.
.
50 mV
13824
3600
50 %
.
.
.
0 mV
0
0
0 %
-0,0036 mV
-1
FFFF
Under range
(9481/..)
(9482/..)
-
-10 mV
-117,6 mV
-2765
-32511
F533
8101
-10 %
-117,6%
<
*1)
*1)
Lower limit exceeded
Short circuit alarm cannot be detected at Resistance and Voltage measurement!
*1) Transmitted value depends on parameterized behavior if an error occurs:
Parameterized behavior if an error occurs
Type of error
Value transmitted if
an error occurs
freeze
All IO-Module errors
Last valid value
Status code
General rule to generate status information in AS
for all AI signals:
Signal is disturbed if value >= 32512 or value<= -32512
see 3.4.1 Behavior of input signals in case of error
Short circuit
*2)
+ / - 32767 7FFF / 8001
Open circuit
*2)
+ / - 32762
7FFA / 8006
Upper limit exceeded
32761
7FF9
Lower limit exceeded
-32760
8008
Cold Junction error
-32752
8010
2 wire calibration failed
-32749
8013
IO-Module does not respond
-32736
8020
Config. unequal from module
-32735
8021
Data not available
-32734
8022
IO-Module hardware error
-32733
8023
*2)
depending of the direction of signal change at the respective error type a positive or negative Status
code is used:
error type
TIM R 9480/..
TIM 9482/.. (R measurement)
TIM mV 9481/..
TIM 9482/.. (mV measurement)
short circuit
-32767 (8001)
not detectable
open circuit
+32762 (7FFA)
-32762 (8006)
For 2 wire calibration of module TIM R 9480/.. and TIM 9482/.. the user interface (LCD display with buttons)
of the CPM 9440 has to be used.
Automatic 2 wire calibration of derTIM modules by short circuit at the end of the line can be used in
combination with 9442 CPUs. Details see the operating instructions of the TIM modules.