UPS for 400 Vac Grid, User Guide, doc. rev. 4
48
For calibration, refer to SolarEdge Customer Service. Field calibrations are not
allowed.
8.2.2.2.
AC output voltage calibration
Use this function if it becomes necessary to recalibrate the voltage readings of any of the UPS's
output phases. Note that this does not refer to the output reading of a particular module but
rather to the output of all modules together.
For calibration, refer to SolarEdge Customer Service. Field calibrations are not
allowed.
8.2.2.3.
Modules input current calibration
Use this function if it necessary to recalibrate the current (ampere) readings of any of the UPS's
input phases. This calibration should be performed on each module, one module at a time, until
all modules have been calibrated. (The value you enter is sent to all modules, so input current
calibration must be performed on one module at a time, with all of the other modules turned off.)
For calibration, refer to SolarEdge Customer Service. Field calibrations are not
allowed..
8.2.2.4.
Modules output current calibration
Use this function if it necessary to recalibrate the current (ampere) readings of any of the UPS's
input phases. This calibration should be performed on each module, one module at a time, until
all modules have been calibrated. (The value you enter is sent to all modules, so input current
calibration must be performed on one module at a time, with all of the other modules turned off.)