UPS for 400 Vac Grid, User Guide, doc. rev. 4
148
Register
Variable name
GET Values
Remarks
278
4x0278
Bypass Apparent Power
Line 2
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
279
4x0279
Bypass Voltage Line 3
×10 VAC
Divide the value by 10 for real measurement:
2315/10=231.5 VAC
280
4x0280
Bypass Current Line 3
×10 A
Divide the value by 10 for real measurement:
21/10=2.1 A
281
4x0281
Bypass Apparent Power
Line 3
×10 kVA
Divide the value by 10 for real measurement:
769/10=76.9 KVA
282
4x0282
Active Alarms Count
Active alarms, except for the ones marked
"ignored" or "for log only" in the controller
configuration
301
4x0301
General Fault
0: Alarm off
1: Alarm on
Any active alarm exists, except for the ones
marked "ignored" or "for log only" in the
controller configuration
302
4x0302
Module 1 Alarm
0: Alarm off
1: Alarm on
303
4x0303
Module 2 Alarm
0: Alarm off
1: Alarm on
304
4x0304
Module 3 Alarm
0: Alarm off
1: Alarm on
305
4x0305
Module 4 Alarm
0: Alarm off
1: Alarm on
306
4x0306
Module 5 Alarm
0: Alarm off
1: Alarm on
307
4x0307
Module 6 Alarm
0: Alarm off
1: Alarm on
308
4x0308
Module 7 Alarm
0: Alarm off
1: Alarm on
309
4x0309
Module 8 Alarm
0: Alarm off
1: Alarm on
310
4x0310
Module 9 Alarm
0: Alarm off
1: Alarm on
311
4x0311
Module 10 Alarm
0: Alarm off
1: Alarm on
312-
318
4x0312- 4x0317 Registers 312 through
318
not relevant for UPS
319
4x0319
Module 18 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
320
4x0320
Module 19 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
321
4x0321
Module 20 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration