4.
If you did not select the Inverter off, and you selected Complete Shutdown the selected
UPS power modules will go into standby state.
8.3.2.2.
Operation > Switch on/off > Modules On
Use this to turn power modules on. After a short wait the load is automatically transferred to the
inverter.
This function reverses a power modules off command.
To turn modules on:
1.
From the System menu select Operation > Turn on/off > Modules on.
The following screen appears:
Figure 97: Turn on/off, Modules on
2.
Select the desired power modules you want to turn on.
The selected power modules will be highlighted in blue.
3.
Click Confirm.