107
UPS for 400 Vac Grid, User Guide, doc. rev. 4
Figure 93: Operation menu
The Static switch snapshot and PQ mode setup functions are only for technician
purposes.
8.3.1.
Operation > Turn on/off > System on/off
This section explains how to turn the UPS on/off.
8.3.1.1.
Operation > Turn on/off > System on
This section explains how to turn the UPS on (following normal shutdown).
To turn the UPS on:
1.
Verify that the input and battery circuit breakers are in the ON position.
If not ON, switch them ON.
The battery circuit breaker is not located on the UPS. It is either on the battery
box or on the cables between the battery box and the UPS.
2.
From the System menu select Operation > Turn on/off.