To reach timer menu from frequency menu press once
.
COMMUNICATION MENU (OPTIONAL)
METERING PRODUCT USE (continued)
Display the required parameter for
modification.
Apply the same procedure as described
in the Setup Menu for network voltage
modification. Possible settings are
described in the previous table.
The COMM menu integrates 4
parameters described in the table
hereunder.
The table explains parameters’ definition,
settings possibilities, and default values.
Communication operation is described in
paragraph 5.
Press
Down push button to access parameter required.
Press
Up push button to come back to previous value
or
Home push button to come back to
.
Parameter modification
Parameter Display
Slave Jbus / Modbus adress
001 to 247
005
Communication Speed
2 400,4 800,9 600,
(baud)
14 400,19 200,
28 800, 38 400
9600
Stop Bit
0,1,2
1
Parity
No, Eve (Even),
No
Odd
Definition
Setting range
Default value
This menu is only
accessible when the option
has been purchased and is
present in the optional slots.
Once plugged into the elec-
tronic module, a 3 minutes
power off action is required
for option identification by
software.
ATI 080 B