36
SOCOMEC - Réf.: 678 623 G GB
VOLTAGE CONFIGURATIONS
VOLTAGE OPTIONS
Standard /- 20%
50 Hz 3 phase 4 wires - 3P4L
60 Hz 3 phase 4 wires – 3P4L
Star connections
Star connections
FG Wilson
Voltage
FG Wilson Voltage
option code
option code
V502
415 / 240V
V603
440 / 254V
(2)
V503
400 / 230V
V605
380 / 220V
V504
380 / 220V
V608
220 / 127V
V507
220 / 127V
V610
208 / 120V
(3)
V510
200 / 115V
(1)
V611
240 / 139V
(1): +20%/-12%
(2): +13%/-20%
(3): +20%/-15%
50 Hz 3 phase 3 (4) wires - 3P3(4)L
60 Hz 3 phase 3 (4) wires – 3P3(4)L
Delta connections
Delta connections
V506
230 / 115V
V606
240 / 120V
V508
220 / 110V
V607
230 / 115V
V609
220 / 110V
50 Hz single phase 3 wire – 1P3L
60 Hz single phase 3 wire – 1P3L
V522
240 / 120V
V622
240 / 120V
V524
230 / 115V
V624
230 / 115V
V526
220 / 110V
V626
220 / 110V
50 Hz single phase 2 wire – 1P2L
60 Hz single phase 2 wire – 1P2L
V521
240V
V621
240V
V523
230V
V623
230V
V525
220V
V625
220V
Optional 277 Vac ( + / -20 % for rating below 630 A, + 20 / -15 % for rating
800 A and above)
50 Hz 3 phase 4 wires - 3P4L
60 Hz 3 phase 4 wires – 3P4L
Star connections
Star connections
FG Wilson
Voltage
FG Wilson
Voltage
option code
option code
V601
480 / 277V
To meet all voltages required by the market, 2 ATI versions have been developed:
CABLE CONNECTIONS BETWEEN SWITCH
AND ELECTRONIC MODULE
A voltage sensing kit is used to provide
sensing and power connections from
the switch terminals to the electronic
module terminals.
The ATI enclosures are delivered as
standard for 3 phases 4 wires applica-
tions, 400 / 230 Vac nominal voltage.
In some 3 phase 4 wires, all 3 phases 3
wires, or single phase 2 or 3 wires
applications, sensing connections keep
the same, but power connections must
be modified according to guidelines
included before connection diagrams.
In standard ATI (bottom
entry) generator cable is
red and main cable is black.
In top entry ATI main cable
is red and generator cable
is black.