INPUTS AND OUTPUT CONTACTS
a
b
c
d
e
Opt. 2 Opt. 1
to lightning protection
option
206
106
ensing
V
o
ltage
7-8
7/
207
11/
73
12/
74
8/
208
9/
209
10/
210
ATI 066 B GB
Identification
Terminals
Type
Feature
Rating
a
207
Inputs Common terminal
or 7
b
207-208
Input
AT Timer inhibit input
or 7-8
Dry contact to close between terminals
7-8 to inhibit AT timer
c
207-209
Input
Remote test on load input
or 7-9
Dry contact to close between terminals 7-9 to start
remotely a test on load (only
available in automatic mode)
d
210 or 10 ( + )
Power supply
Power supply dedicated
to lightning option
207 or 7 ( - )
5 Vdc < V
7-10
< 16 Vdc without load
9 Vdc < V
7-10
< 10 Vdc for 1 to 2 inputs
e
73-74
Output
Start Gen signal
or 11-12
30 V DC – 1 A
-
Max dir
ect voltage 30 Vdc
-
Min dir
ect voltage 10 Vdc
- Max inverse voltage 30 Vdc
- Galvanic insulation 3
k
V
(1 min 50
Hz)
-
Min pulse duration 1 s
-
Max number of operations 10
8
CURRENT INPUTS
(for METERING)
201
202
203
204
205
206
101
102
103
104
105
106
1
3
N
2
1
3
N
2
Puissance 230 V AC - - Mesur
e de tension
Mesur
e de tension – O
O – Puissance 230 V AC
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
I1
I2
I3
T2
T1
S2
S1
R2
R1
LOAD
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
Short circuit plug
delivered with the spare part
R1 R2 S1 S2 T1 T2
ATI 090 B GB
If the load is supplied, before discon-
necting the main connector, it is
necessary to short-circuit the secondary
of the current transformer (short-circuit
plug to be mounted).