Source availability
• 2 green Leds to indicate if
Gen and Mains sources are available
(voltage and frequency measurement)
- Led is on = source available
- Led is off = source missing
Retransfer Inhibit
• 1 yellow Led, linked to
retransfer inhibit pushbutton
- Led is on = retransfer
inhibit feature is active
- Led is off = retransfer
inhibit inactive
- Led is blinking = retransfer
is blocked, waiting for a push
on the retransfer inhibit
pushbutton to allow retransfer
Switch state
• 2 green Leds to indicate if
the switch is opened or closed
- Led is on = switch is closed
- Led is off = switch is opened
• 1 Yellow led to indicate if both
switches are in 0 position
- Led is on = both switches opened
- Led is off = Gen or Mains
switch closed
Error Led
• 1 red led to indicate a fault
- Led is on = switch error
Action from software not confirmed by an auxiliary
contact. Reset after power off
- Led blinks in case of lightning protection operation
No reset required (blinking disappears once input is low)
Power Led
• 1 green led
- Blinks slowly as soon
as the product is powered
and software runs correctly
- Always on = Power OK and
software error
- Always off = Power off or
software error if another
led is on and LCD is OK
Keyswitch
• Insert key to allow switch
operational mode modification
• Turn right to access automatic mode
• Turn left to access manual mode
Padlock
• Pull the yellow handle to allow padlock insertion
• Padlocking possible in position 0,1 or 2
but only in Manual mode (keyswitch position),
handle out of housing.
Keypad
Switch Position Indications
• 0, 1 or 2 position display
Manual Operation
• Insert handle to manually
operate the switch.
• Manual operation only possible
in Manual mode (keyswitch),
when not padlocked
Modes annunciation and Tests
• 1 Top yellow led for Manual Mode position linked
to the key position
• 1 green led for Automatic Mode position linked
to the key position
• 2 Bottom yellows leds for Test On and
Off Load position Linked to the test pushbutton press
Symbols are represented to make comprehension easier
LCD
• Larger LCD to display information.
Push button
• : Home push button during programming
• : Lamps test button
SOCOMEC - Réf. : 678 623 G GB
61
ENGL
ISH
METERING PRODUCT USE
GENERAL INTRODUCTION
The product provides sources availability
monitoring, Automatic / Manual Retransfer,
Manual / Automatic or Test operation
monitoring, voltage and frequency metering,
and good operation or error information. The
product provides sources …error information.
Furthermore, the metering module allows
current and power metering on a large back-
lited display.
The product requires at least one type of
network configuration and a network nominal
voltage configuration to be input via the
keypad by the user.
Other default values can be kept or modified
according to hereafter programming guide-
lines.
ELECTRONIC MODULE USAGE
The electronic module is directly mounted
on the motorized block.
It integrates the following features:
- Voltage and frequency metering
- Automatic transfer controls
Following diagram introduces product
front panel.
Led indication is only active once the
product is powered (power led
activated).
Front Panel Introduction
Verify power applied on the
electronic module power inputs
terminals 101-102 or 201-202
before powering up the unit.
ATI 067 A
ATI 068 B