SOCOMEC - Réf.: 678 623 G GB
23
ENGL
ISH
OPTIONAL CONNECTIONS
ENCLOSURES INSTALLATION (continued)
Metering :
- (Sensing) CTS
- Specific Metering Display
f
1
2
0 A/M
Padlocking
g h
i
j
20/
13
21/
14
22/
24
23/
34
24/
43
25/
44
26/
53
27/
54
Option 1
Me Auxiliary contacts Option
Available from third release 2004. This
option is factory fitted and includes a
specific metering d metering
CTs to allow c power metering.
Auxiliary contacts for 0,1,2 position,
padlock and Auto/Manual Mode.
Available from factory.
Verify there is no voltage
on the terminals before
mounting the options.
ATI 049 B GB
Contact f, g and h are closed when the
switch is in position 1, 2 or 0.
Contact i is closed when the switch is
in Automatic mode.
Contact j is closed when the switch is
padlocked.
Identification
Terminals
Type
Feature
Rating
f
13-14
Output
Position 1 Auxiliary contact
or 20-21
Contact closed when
switch is in position 1
g
13-24
Output
Position 2 Auxiliary contact
or 20-22
Contact closed when
switch is in position 2
h
13-34
Output
Position 0 Auxiliary
or 20-23
contact Contact closed
when switch is in position 0
i
43-44
Output
Auto / Manu information
or 24-25
Contact closed when
Automatic mode is active
j
53-54
Output
Padlocking information
or 26-27
Contact closed when
the switch is padlocked
• Resistive load: 10 A • Inductive load: 3 A
Max V
ac: 250 - Max operations: 5 x 10
7