SOCOMEC - Réf.: 678 623 G GB
BASIC PRODUCT USE (continued)
This sequence is started as soon as the
unit is in automatic mode and in posi-
tion 2.
Position 2:
• Mains is not available
• Switch is in position 2 (Generator)
• Generator is off
Retransfer Inhibit Feature
• Once the Mains is back, it might be
preferable not to immediately transfer
the load from the generator to the
mains.
• If Retransfer inhibit feature has been
enabled in the programming mode,
the RTI led is on (default value).
• Once retransfer from the Generator
to the Mains is ready, RTI feature
blocks the retransfer and the RTI led
is blinking.
• A manual press on the RTI push but-
ton is necessary to start retransfer.
MAINS RETURN AUTOMATIC SEQUENCE
Specific features
RTI Led
RTI pushbutton