20
SOCOMEC - Réf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
800 A/1000 A ratings Top cable entry
A
A
536
480
520
720
28
30
14
200
775
1175
600
623
1375
80
50
50
80
536
480
120
50
14
12
13
1
3
Torque: M10
26Nm (Max)
M12
45Nm (Max)
Phase and neutral cable:
800A:3x240mm
2
or 2x300mm
2
(Max)
1000A:4x240mm
22
or 2x300mm
2
(Max)
Earth cable:
-800A:2x120mm
2
or 1x300mm
2
(Max)
-1000A:2x240mm
2
or 1x300mm
2
(Max)
A-A
Main
Load
Generator
ATI 048 C GB
Power Cables Connection