BASIC PRODUCT USE (continued)
ON LOAD TESTING
This test is only possible in automa-
tic mode in position 1 and Mains
available.
Description :
• This test simulates a loss of mains
condition. Loss of Mains sequence is
started and Mains return sequence
automatically activated as soon as
generator is available.
• All timers are run following their set-
ting.
• The retransfer inhibit feature is
always activated during test on load
(from keypad).
Press Test pushbutton to make test
on load Led blinking and press vali-
dation pushbutton to start the cycle,
Following Loss of Mains + Mains
return sequences.
Keypad activation
It is possible to remotely start the test
on load closing contacts 7 and 9 on
the electronic module.
The cycle is started as soon as the
input is closed.
The retransfer from generator to mains
is blocked, and only allowed once the
input is de activated.
Remote activation via remote test
on load input