6
SOCOMEC - Réf.: 678 623 G GB
ENVIRONMENT
• Ingress protection of IP41 with overall
rating of IP21
• Operating temperature of – 10 °C to
40 °C without de-rating
• Operating temperature of 40 °C to
65 °C with de-rating
The complete enclosure meets following environmental requirements:
INTRODUCTION (continued)
TECHNICAL CARACTERISTICS
Characteristics
Thermal Current Ith (40 °C)
250 A
400 A
630 A
800A
1 000A
1250 A
1600 A
Assigned isolement voltage Ui (V)
800
800
1 000
1 000
1 000
1000
1000
Assigned voltage to chocks Uimp (kV)
8
8
12
12
12
12
12
IEC 60947-6-1 Characteristics
Assigned current Ie (A) (B categorie)
415 Vac AC31B
250
400
630
800
1 000
1250
1600
Operating Class
Material class
PC
PC
PC
PC
PC
PC
PC
Maximum short circuit current using gG DIN fuse
Max short circuit (kA eff)
50
18
70
50
100
100
100
Fuse size (A)
250
400
630
800
1 000
1250
2 x 800
Peak current value: withstand and closing operation (kA peak)
23
23
45
48
75
75
75
Short circuit Operation
Rated short time withstand current (kA eff)
10
10
12.6
16
20
25
32
Rated short circuit making capacity (kA max)
17
17
25.2
27.2
40
52.5
67
Other Characteristics
Commutation duration
I-II ou II-I (s)
(1)
1.3
1.3
1.3
2.6
2.6
2.8
2.8
I-o ou II-0 (s)
(1)
0.85
0.85
0.85
1.6
1.6
1.7
1.7
Black time durating during commutation under Un (ms)
600
600
600
1 500
1 500
1700
1700
Power input
230 Vac mini / maxi (V)
184/276
184/276
184/276
184/276
184/276
210/310
210/310
277 Vac mini / maxi (V) - Option 5
221/332
221/332
221/332
221/332
221/332
240/380
240/380
Consumption during switching operation
230 Vac maxi / average (VA)
400/100
400/100
420/110
450/120
450/120
470/128
470/128
277 Vac maxi / average (VA) - Option 5
400/110
400/110
420/115
450/125
450/125
470/128
470/128
Mechanical characteristics
Number of commutation (durability)
8 000
8 000
5 000
4 000
4 000
3000
3000
Weight (complete std enclosure) kg
39
44
66
125
130
230
330
All these characteristics are given as information and are not contractual
(1): Between order sent and final position (under nominal conditions)
Temperature Derating
Nominal Rating
Cable Size
De rate
IEC 947-3
(40 °C Max)
50 °C
60 °C
65 °C
40 °C 415 V
60 °C 415 V
(A)
(mm
2
)
(A)
(A)
(A)
AC 22
AC 23
AC 22
AC 23
250
120
250
220
200
AC23A 250A
AC23A 200A
400
240
360
300
250
AC22A 400A
AC23A 250A
AC23A 250A
630
2 x 185
550
500
400
AC22A 630A
AC23A 500A
AC23A 400A
800
2 x 240
720
640
540
AC22A 800A
AC23A 800A
AC23A 540A
1 000
4 x 150
880
800
680
AC22A 1000A
AC23A 1000A
AC23A 680A
1 250
4 x 240
1 150
1 000
820
AC22A 1 250A
AC22A 1 000A
1 600
5 x 240
1 300
1 100
930
AC22A 1 600A
AC22A 1 100A
Single phase configuration
Table available for single phase configurations using a 4 poles switch and connecting 2 poles in parrallel
Max ambiant Temperature = 40 °C
Nominal Rating 3 phase configuration
Nominal Rating 1phase configuration
(A)
(2 poles in //) (A)
250
400
(1)
Short circuit level required for 630A
400
630
(1)
not acceptable for 400A version
630
800
(2)
(2)
Short circuit level required for 800A
800
1 250
not acceptable for 630A version
1 000
1 600
(3)
(3)
Short circuit level required for 1 600A
1250
1 800
not acceptable for 1 000A version
1 600
2 500
(4)
(4)
Short circuit level required for 2 500A
not acceptable for 1 600A version
Metering accuracy
Voltage and frequency: 1 % on power input range.
• 95 % humidity non condensing at
40 °C
• Maximum operating altitude without
switch de-rating is 2 000 m above
sea level.
• Maximum storage is one year at:
- Maximum tempe55°C
- 95% humidity non condensing
• 80 % humidity non condensing at