- 82 -
4
The electric
actuator does
not move at all.
Lock release
error
Check if you can hear the
sound of lock release
when the manual lock
switch is turned on and
off.
If there is no sound of lock release from the
electric actuator with lock, the lock may be
broken.If the trouble continues, please
contact SMC.
External device
fault
Check that the PLC
connected to the driver
operates correctly.
Check that it operates with a test run of the
driver alone.
If it is operated, a signal output from the
PLC is suspected.
Take appropriate measures by referring to
the Operation Manual for the driver.
→
6.3 Parallel I/O signal is detailed
Inappropriate
specifications
Check that the
combination of the electric
actuator and driver is
correct?
Check if the product number of the used
electric actuator matches with the electric
actuator which is applicable to the driver.
→ 3. Product Specifications
Stop command
If it is not energized,
the servo will be OFF
and does not operate.
Check if a voltage of 24
VDC is applied to the
EMG terminal.
Apply 24 VDC to the EMG terminal.
Incorrect signal
input
Check that the driver is
ready to operate with the
pulse signal.
If the pulse signal cannot operate the
driver, the cause may be one of the
following.
1. Servo is OFF: Turn ON the servo.
2. CLR input is ON
: Turn OFF the CLR input.
3. Returning-to-origin
: Do not input the pulse signal.
4. Test run from the controller setting
software/teaching box
: Do not input the pulse signal.
Incorrect
parameters
Confirm that the pulse
input signal input method
is correct.
Make sure that the pulse signal input
method is correct.
→
7.2 Basic parameter
Move
occasionally
Wiring fault
Is the wiring connected
correctly?
Check if the wiring is connected correctly or
if there is broken wire or short-circuit by
referring to this Operation Manual. Correct
the wiring and check that the input/output of
each signal is correct.
Separate the power supply for the
CN1driver and the CN5 I/O signal power
supply.
→ 4. External Wiring Diagram
→ 6.4 Parallel I/O Wiring Example
Electric noise
Check that the Grounding
is connected correctly?
Are power cables for other
equipment and driver
cables bundled together?
Connect to Ground correctly.
Avoid bundling the cables with power
cables of other equipment.
Take appropriate measures by referring to
the Operation Manual for the driver.
→ 3.4 How to install
Inappropriate
parameter
Check that the parameter
values are correct.
Check the combination of the electric
actuator and driver. Modify the parameters
accordingly and check the operation.
→ 7. Setting Data Entry