- 67 -
Overflow
ALM
[6C]
(
1-108
)
C
RESET
SVON
input
<Contents>
Position deviation counter in the driver has overflowed during the
operation by pulse signals.
<Countermeasure>
Make sure there are no obstructions that interfere with the
electric
actuator movement. Also, make sure that the load, speed, acceleration
and deceleration are within the range of the
electric
actuators.
Over speed
(
1-144
)
D
RESET
SVON
input
<Contents>
The motor speed exceeds a specific level due to an external force, etc.
<Countermeasure>
Make improvements such that the motor speed will not exceed the
maximum speed of the
electric
actuator.
Caution
Please refer to the manual or the catalogue of the
electric
actuator for
the maximum speed of the
electric
actuator.
Over motor
Vol
(
1-145
)
D
RESET
SVON
input
<Contents>
The motor power-supply voltage detected in the driver is outside the
specified range. The driver checks the lower limit of the motor power
supply voltage only when the servo ON is commanded.
<Countermeasure>
Make sure that the voltage supplied to the motor power (M24V) of the
driver is within specification.
Caution
If the power supply is “inrush current control type”, a voltage drop may
cause an alarm during acceleration/ deceleration.
Over motor
Vol
(
1-145
)
D
RESET
SVON
input
<Contents>
The alarm may be increased by regenerative power depending on the
method of operation of the electric actuator.
<Countermeasure>
Make sure that the operating conditions are within the specifications.
Caution
Please refer to the manual or the catalogue of the
electric
actuator for
the method of operation of the
electric
actuator.
Over Temp.
(1-146)
D
RESET
SVON
input
<Contents>
The temperature around the power element of the driver is too high.
<Countermeasure>
Make improvements so that the temperature around the driver is kept
appropriate.