- 73 -
No.JXC#-OMX0009-A
14.2 When supplying power for the first time
Please refer to the following [Procedures and Timing diagram] for each operation.
-Procedure- -Timing diagram-
1) Supply power
↓
2) ESTOP output is turned OFF
ALARM output is turned ON
OUT3 output is turned ON
([1-153: Absolute encoder ID does
not match controller data] alarm is
generated)
↓
3) RESET is turned ON.
↓
4) ALARM output is turned OFF.
↓
5) SVON input is turned ON
↓
6) SVRE output is turned ON.
* The actuator with lock is unlocked.
↓
7) SETUP input is turned ON.
↓
8) BUSY output is turned ON.
(Starts the operation.)
↓
9) SETON, INP output turns ON.
Return to origin is completed when
BUSY output is turned OFF.
When return to origin operation is
completed, DRIVE is available.
T1: 1.6 s or less (System initialize time + Time required to activate alarm)
T2: Communication cycle time: 2 times or more
-
-
-
-
-
-
-
-
-
-
Power
Input
signal
Output
signal
24V
0V
ON
OFF
ON
OFF
・
・
・
・
・
・
・
・
・
・
・
・
・
・
0mm/s
Unlock
Hold
T1
T2
External lock
Speed