- 62 -
No.JXC#-OMX0009-A
11.2 Basic parameters
The "Basic parameter" is the data to define the operating conditions of the controller, conditions of the
actuator, etc.
Activation: “XX” = Become effective just after recorded into the controller
“X” = Become effective after restarting the controller
“
-
”= The parameter cannot be changed (fixed value)
Basic parameters
.
Parameter
name
Input
range
Details
Acti
vati
on
Controller ID
1 to 32
Identification number (axis) parameters of serial communications
(communication with PC, teaching box) are set.
X
I/O pattern
Fixed value
This is a fixed value for the controller. Do not change the setting.
(Default value is “1”)
-
ACC/ DEC
pattern
Fixed value
This is a fixed value for the controller. Do not change the setting.
(The default value varies depending on the electric actuator)
-
S-motion rate
Fixed value
This is a fixed value for the controller. Do not change the setting.
(The default value varies depending on the electric actuator)
-
Stroke (+)
*1)
This defines the positive (+) side limit of the position. (Unit: mm)
Any value greater than the [stroke (+)] value cannot be entered in the
“Position” field data of step parameter setup.
XX
Stroke (-)
*1)
This defines the positive (-) side limit of the position. (Unit: mm)
Any value greater than the [stroke (+)] value cannot be entered in the
“Position” field data of step parameter setup.
XX
Max speed
*1)
This defines the maximum limit of the speed. (Unit: mm/s)
Any value greater than the [stroke (+)] value cannot be entered in the
“Position” field data of step parameter setup.
XX
Max ACC/DEC
*1)
This defines the maximum settable acceleration. (Unit: mm/s
2
)
Any value greater than the [Max ACC/DEC] value cannot be entered
in the “Accel” field data of step parameter setup.
XX
Def In position
*1)
This defines the range to activate the INP when the actuator is within it
after the return to origin operation.(Unit: mm)
XX
Caution
Writing of the parameter should be performed while the electric actuator is stopped.