- 61 -
No.JXC#-OMX0009-A
Pushing
speed
Pushing
speed
Minimum
value to “Max
force” of the
basic
parameter
*1)
■Effective only for the pushing operation
(when the value for the "Pushing force" is from 1 to 100).
This defines the movement speed during the pushing operation. If
this Speed is too high, it may cause damage to the actuator or
work piece due to impacts. Therefore, enter a value within the
range appropriate for the actuator. (Unit: mm/s)
Please refer to the actuator manual for the appropriate range of the
speed.
■For the positioning operation, this value is ignored.
Moving force
Moving force
*1)
The setting to define the maximum torque during the positioning
operation.
Enter a value within the range appropriate for the actuator.
(Unit: %)
Please refer to the actuator manual for the appropriate range of the
speed.
AREA 1
AREA 1
“Stroke (-)” to
“Area2” of step
data
The setting to define the conditions where “AREA” will turn ON.
(Unit: mm)
If the current position is within the range between Area1 and Area2,
the “AREA” signal will turn ON.
If Area1 > Area2, the alarm "Step Data ALM1" will be activated.
(However, no alarm is generated if "Area1" = "Area2" = 0, the
“AREA” signal will be OFF).
AREA 2
AREA 2
“Area1” of step
data to “Stroke (+)”
of
the
basic
parameter
In position
In position
*1)
The functions of this will be different between the pushing operation
and the positioning operation.
Positioning operation: Positioning range (Unit: mm)
Pushing operation: Pushing distance (Unit: mm)
Movement
mode
Details
Positioning
operation
This is the setting to define the conditions where
“INP” will turn ON.
When the actuator enters within this range from
the target position, “INP” will turn ON.
(It is not necessary to change this from the initial
value).
If it is required to receive a signal before the
actuator completes the positioning operation, this
value should be larger.
“INP” will turn ON.
Target position -
in position ≤ actuator position
≤ target po in position
Pushing
operation
This is the setting to define the distance pushed
by the actuator during the pushing operation.
When the actuator has exceeded this distance,
the pushing operation will end. In this case, “INP”
will not turn ON.
*1 The range varies depending on the electric actuator. Please refer to the manual of the electric
actuator for more details.