- 82 -
No.JXC#-OMX0009-A
(7) Check that data is being transmitted and the transmission is completed by using the same
procedures described in (3) and (4).
When data transmission is completed, [Position] of the step data No. 1 is output to the remote register
RWr6 to 7: DATA.
RWr6
:
DATA (H)
=
(0000)h
RWr7
:
DATA (L)
=
(1388)h
(8) Check that the Step data is edited correctly. In order to complete the data editing, confirm ON of
“Sending completed” by OFF of the Start flag, and then set the OFF flag of the remote register
RWw0,bit1: Setting parameter rewriting.
For the memory address used in the data editing function in the full numeric data instructions mode,
please check
"10.2 Remote register (RWr and RWw)".
Setting parameter
Data
Power
Sending
Sending completed
Input
Start flag
rewriting
(SubFunction etc)
DATA(H,L)
Output
24V
0V
ON
OFF
ON
OFF
・
・
・
・
・
・
・
・
(2)
(3)
(4)
(1)
(5)
(6)
(7)
(8)
Min 15ms
Min 15ms