[4] HOLD
- Procedure -
- Timing chart HOLD -
①
During operation (“BUSY” is ON),
turn ON “HOLD”.
↓
②
“BUSY” turns OFF.
(The actuator stops.)
↓
③
Turn OFF the “HOLD”.
↓
④
“BUSY” turns ON.
(The actuator restarts.)
[5] Reset
-Procedure- [Driving reset]
①
During operation (“BUSY” is ON)
“RESET” is turned ON
↓
②
“OUT0” to “OUT5” are OFF.
↓
③
“BUSY” are OFF. (The electric actuator stops.)
-Procedure- [Alarm Reset]
①
Alarm generated
(ALARM output turns OFF, OUT0 to OUT3
turn ON.)
↓
②
Turn ON “RESET”.
↓
③
ALARM output turns ON, OUT0 to OUT3
turn OFF. (The alarm is deactivated.)
[6] Stop
- Procedure -
①
During operation (“BUSY” is ON),
turn OFF “EMG”. (Stop command)
↓
②
“ESTOP” turns OFF.
↓
③
“BUSY” turns OFF. (The actuator stops.)
“SVRE” turns OFF.
The
electric actuator with lock is locked.
↓
④
Turn ON “EMG”. (The stop release command)
↓
⑤
“ESTOP” turns ON.
“SVRE” turns ON.
The
electric actuator with lock is unlocked.
When "Stop [EMG]" is OFF, the stop is activated.
-Timing chart Alarm reset
If the electric actuator is within the “In position” range, INP will be turned ON.
-Timing chart Driving reset -
-
Timing chart stop
-
RESET
OUT0 to 5
BUSY
INP
Electric actuator
Speed
Output
Input
ON
OFF
ON
OFF
ON
OFF
OFF
ON
0mm/s
Deceleration
starts
HOLD
BUSY
Electric actuator
HOLD during the operation
Input
Output
Deceleration
starts
Speed
0mm/s
ON
OFF
ON
OFF
Power
Stop[EMG]
SVON
BUSY
SVRE
SETON
INP
ALARM
ESTOP
External Lock
Electric actuator
Emergency stop during operation
Output
Input
If the actuator is w ithin the "In
position" range, INP w ill be
turned ON but if not, it w ill
remain OFF.
Deceleratio
n starts
Speed
0mm/s
24V
0V
OFF
ON
ON
OFF
ON
OFF
・
・
・
・
・
・
・
・
・
・
・
ON
OFF
RESET
OUT0
~
5
ALARM
Output
Input
Alarm is generated
ON
OFF
ON
OFF
ON
OFF