HRX-OM-M005
Chapter 5 Product Operation
HRZD Series
5.3 Operation Screen
5-33
5.3.22 CH1(2)DIO communication setting screen 2
Figure 5-47 “CH1(2)DIO Communication Setting Screen 2”
Table 5-25 “CH1(2)DIO Communication Setting Screen 2”
No.
Item
Setting range
Descriptions
Factory default
1
RUN
A_1, M_1, M_2, N/A
Allows the setting of the
start (input) signal aspect.
A_1
2
REMOTE
A_1, M_1, M_2, N/A
Allows the setting of the
remote (input) signal
aspect.
N/A
Alarm1
to Alarm
32
A relevant alarm is raised.
Run
The product goes into action.
W&F
An alarm is raised.
Fault
Fault alarm is raised.
Warning Warning alarm is raised.
Flow
OK
Circulating fluid reaches a flow
rate required for operation.
Ready
RDY lamp on the Main screen
comes on.
Remote
DIO REMOTE mode is
established for communication.
Purge
Circulating fluid is recovered.
3
OUT1 to OUT6
[Numbers
following
OUT1 to OUT6
refer to P1/P2
contact signal
connector pin
numbers.]
N/A
Output signal: OFF (open) for
normal operation
The output signal status
switches once the product
enters a set state.
A setting-switching status
relationship conforms to
the setting range.
4
OUT1 to OUT6 Contact A, B
Output signal
A: Contact A, B: Contact
B
Same as above
5 [Enter]
key
―――
Used to display the
“MESSAGE screen” to
accept the setting.
-
6 [Initial]
key
―――
Used to display the
“MESSAGE screen” to
initialize the settings of
RUN, REMOTE, and
OUT1 to OUT6.
-
7 [Cancel]
key
―――
Used to cancel the
setting.
-
8 [Return]
key
―――
Used to display the
“CH1(2)DIO
communication setting
screen 1” on page 5-32.
-
7 8
2
6
5
1
3
4
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
Run
Contact A
Warning
Contact B
Fault
Contact B
Remote
Contact A
Ready
Contact A
W&F
Contact B