HRX-OM-M005
Chapter 5 Product Operation
5.3 Operation Screen
HRZD Series
5-10
Procedure for changing circulating fluid set temperature
1.
Touch the [SETTING] key in “CH2” on
the “Main screen”.
The “CH2 Setting Data screen 1” is displayed.
Figure 5-12 “Main Screen”
2.
Touch the [SET] key for “TEMP SP”.
The “Ten-key screen” is displayed.
Figure 5-13 “CH2 Setting Data Screen 1”
3.
Use the ten-key to input a set value, and
touch the [ENT] key.
The setting of the TEMP SP set value takes place,
and the “CH2 Setting Data screen 1” is
displayed.
Figure 5-14 “Ten-key Screen”