HRX-OM-M005
Chapter 3 Transporting and Installation
3.3 Procedure for Installation
HRZD Series
3-14
Procedure for piping installation
Secure the pipe coupling section with a pipe wrench, and provide proper tightening
to the pipe.
Recommended piping installation
Table 3-4 Recommended Pipe
No.
Name
Size
Material
1 Valve
Rc3/4
Stainless
steel
2
Y-strainer (100
μ
m)
Rc3/4
Stainless steel
3 Valve
Rc1/2
Stainless
steel
4
Y-strainer (5
μ
m)
Rc1/2
Stainless steel
Figure 3-10 Pipe Tightening
Pipe coupling section
Figure 3-11 Recommended Piping Installation
System on the
customer side
CH1 circulating fluid
supply
CH1 circulating fluid
return
Facility water inlet
Facility water outlet
CH2 circulating fluid
supply
CH2 circulating fluid
return