HGM8151 Genset Parallel Controller User Manual Page 31 of 66
No.
Items
Parameters
Defaults
Description
1: Open to active
Digital Input Port 7
1
Contents Setting
(0~55)
0
User defined.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
3
Active Range
(0~3)
3
0: From safety on 1: From starting 2:
Always active 3: Inactive
4
Active Actions
(0~4)
4
0: Warn; 1: Shutdown; 2: Trip and stop 3:
Trip 4: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting input port is active to
confirm.
6
Description
LCD display detailed contents when the
input is active.
Digital Input Port 8
1
Contents Setting
(0~55)
15
Reserved.
2
Active Type
(0~1)
0
0: Closed to active
1: Open to active
Relay Output Ports
Relay Output Port 1
1
Contents Setting
(0~299)
44
Generator OK.
2
Output Type
(0~1)
0
0: Normally open;
1: Normally close
Relay Output Port 2
1
Contents Setting
(0~299)
48
Common Alarm.
2
Output Type
(0~1)
0
0: Normally open;
1: Normally close
Relay Output Port 3
1
Contents Setting
(0~299)
38
Energize to Stop.
2
Output Type
(0~1)
0
0: Normally open;
1: Normally close
Relay Output Port 4
1
Contents Setting
(0~299)
35
Idle Control.
2
Output Type
(0~1)
0
0: Normally open;
1: Normally close
Relay Output Port 5
1
Contents Setting
(0~299)
30
Gen Open Output.
2
Output Type
(0~1)
0
0: Normally open;
1: Normally close
Relay Output Port 6
1
Contents Setting
(0~299)
29
Close Gen Output.
2
Output Type
(0~1)
0
0: Normally open;
1: Normally close