HGM8151 Genset Parallel Controller User Manual Page 41 of 66
No.
Type
Description
20
Black Start
21
Alarm Stop Inhibit
All shutdown alarms are prohibited except emergence stop.(Means
battle mode or override mode)
22
Aux Instrument Mode
All outputs are prohibited in this mode.
23
Non-parallel Mode
24
Reset Maintenance Alarm
Controller will set maintenance time and date as default when input
is active.
25
Reserved
26
High Temp Shut
Connected sensor digital input.
27
Low Oil Pressure Shut
Connected sensor digital input.
28
Remote Start
(On Load)
In
Auto
mode, when input is active, genset can be started and with
load after genset running normal; when input is inactive, genset will
stop automatically.
29
Remote Start
(Off Load)
In
Auto
mode, when input is active, genset can be started and
without load after genset running normal; when input is inactive,
genset will stop automatically.
30
Manual Start Auxiliary
In
Auto
mode, when input is active, genset will start automatically;
when input is inactive, genset will stop automatically
31
Remote Start
(On Demand)
32
Reserved
33
Simulate Stop Button
An external button can be connected and pressed as the simulate
panel key.
34
Simulate Manual Button
35
Reserved
36
Simulate Auto Button
An external button can be connected and pressed as the simulate
panel key.
37
Simulate Start Button
38
Simulate Gen Load Button
This is simulating generator switch close button.
39
Simulate
Mains
Load
Button
This is simulating generator switch open button.
40
NEL Manual Trip
41
NEL Manual Reconnection
42
Power Management Mode
43
Mains Parallel Mode
44
First Priority
45
Reserved
46
Reserved
47
Configuration 1
Users can set different parameters to make it easy to select
current configuration via input port.
48
Configuration 2
49
Configuration 3
50
Balance Test
51
Speed Raise
52
Speed Drop