HGM8151 Genset Parallel Controller User Manual Page 29 of 66
No.
Items
Parameters
Defaults
Description
controller re-power on.
GSM Setting
1
GSM Enable
(0-1)
0
0: Disable; 1: Enable
2
Phone Number Set
Max. 20 bit
Phone number needed to be added area
code of region or country.
e.g. China 8613666666666
Scheduling and Maintenance Setting
1
Scheduled Run
(0~1)
0
0: Disable; 1: Enable
2
Scheduled Not Run
(0~1)
0
0: Disable; 1: Enable
3
Maintenance
(0~1)
0
0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1
Curve Type
(0~15)
7
SGX
2
Open Circuit Action
(0~2)
0
0: Warn 1: Shutdown 2: No action
3
High
Temp.
Shutdown
(0-300)ºC
98
Shutdown when sensor temperature higher
than this value. Detecting only after safety
delay is over. The delay value (default: 3s)
also can be set.
4
High Temp Warn
(0-300)ºC
95
Warn when sensor temperature higher than
this value. Detecting only after safety
delay is over. The delay value (default: 5s)
and return value (default: 93) also can be
set.
5
Low Temp. Warn
(0~1)
0
0: Disable; 1: Enable
Oil Pressure Sensor
1
Curve Type
(0~15)
7
SGX
2
Open Circuit Action
(0~2)
0
0: Warn 1: Shutdown 2: No action
3
Low OP Shutdown
(0~1000)kPa
103
Shutdown alarm will be sent when oil
pressure of external oil pressure sensor
lower than this value. Detecting only after
safety delay is over. The delay value
(default: 3s) also can be set.
4
Low OP Warn
(0~1000)kPa
124
Warn when oil pressure of external oil
pressure sensor lower than this value.
Detecting only after safety delay is over.
The delay value (default: 5s) and return
value (default: 138) also can be set.
Fuel Level Sensor
1
Curve Type
(0~15)
0
Not used.
2
Open Circuit Action
(0~2)
0
0: Warn; 1: Alarm Shutdown; 2: No Action
3
Low Fuel Level Warn (0~300)%
10
When liquid level value of the external liquid
level sensor is lower than the set value, low