HGM8151 Genset Parallel Controller User Manual Page 37 of 66
No.
Type
Description
63
PWM Voltage Raise
When output type of AVR set as “Relay output”, controller
adjust voltage and reactive power via
“Sync Raise Volt” and
“Sync Drop Volt”
.
64
PWM Voltage Drop
65
PWM Speed Raise
When output type of GOV set as “Relay output”, controller
adjust speed and power via
“Sync Raise Speed” and “Sync
Drop Speed”
.
66
PWM Speed Drop
67
Reserved
68
Reserved
69
Digital Input 1 Active
Action when input port 1 is active.
70
Digital Input 2 Active
Action when input port 2 is active.
71
Digital Input 3 Active
Action when input port 3 is active.
72
Digital Input 4 Active
Action when input port 4 is active.
73
Digital Input 5 Active
Action when input port 5 is active.
74
Digital Input 6 Active
Action when input port 6 is active.
75
Digital Input 7 Active
Action when input port 7 is active.
76
Digital Input 8 Active
Action when input port 8 is active.
77~80 Reserved
81~96
Expand Digital Input 1-16
Active
Action when extension digital input ports 1-16 are active.
97~98 Reserved
99
Emergency Stop
Action when emergency stop alarm.
100
Fail to Start
Action when failed start alarm.
101
Fail to Stop
Action when failed stop alarm.
102
Under Speed Warn
Action when under speed alarm.
103
Under Speed Shutdown
Action when under speed shuts down.
104
Over Speed Warn
Action when over speed warn.
105
Over Speed Shutdown
Action when over speed shutdown alarm.
106
Reserved
107
Reserved
108
Reserved
109
Gen Over Freq. Warn
Action when generator over frequency warning.
110
Gen over Freq. Shutdown
Action when generator over frequency shutdown alarm.
111
Gen Over Volt Warn
Action when generator over voltage warning.
112
Gen Over Volt Shutdown
Action when generator over voltage shutdown.
113
Gen Under Freq. Warn
Action when generator low frequency warning.
114
Gen Under Freq. Shutdown
Action when generator low frequency shutdown.
115
Gen Under Volt. Warn
Action when generator low voltage warning.
116
Gen Under Volt. Shutdown
Action when generator low voltage shutdown.
117
Gen Loss of Phase
Action when generator loss phase.
118
Gen Phase Sequence Wrong Action when generator reverse phase.
119
Reserved
120
Over Power Alarm
Action when controller detects generator have over power.