HGM8151 Genset Parallel Controller User Manual Page 60 of 66
16.12
MTU ADEC (SMART MODULE)
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Table 35 ADEC (X1 Port)
Terminals of controller
ADEC (X1 port)
Remark
Fuel relay output
X1 10
X1 Terminal 9 Connected to negative of
battery
Start relay output
X1 34
X1 Terminal 33 Connected to negative of
battery
Table 36 SMART (X4 Port)
Terminals of controller
SMART (X4 port)
Remark
CAN GND
X4 3
CAN
communication
shielding
line
(
connect to controller’s this te
rminal only)
CAN(H)
X4 1
Using impedance 120Ω connecti
ng line
CAN(L)
X4 2
Using impedance 120Ω connecting line
Engine type: MTU-ADEC.
16.13
MTU ADEC (SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Table 37 ADEC (X1 Port)
Terminals of controller
ADEC (X1port)
Remark
Fuel relay output
X1 43
X1 Terminal 28 Connected to negative of
battery
Start relay output
X1 37
X1 Terminal 22 Connected to negative of
battery
Table 38 SAM (X23 Port)
Terminals of controller
SAM (X23 port)
Remark
CAN GND
X23 3
CAN
communication
shielding
line
(connect with controller’s th
is terminal
only)
CAN(H)
X23 2
Using impedance 120Ω connecting line
CAN(L)
X23 1
Using impedance 120
Ω connecting line
Engine type: Common J1939.