HGM8151 Genset Parallel Controller User Manual Page 12 of 66
phase and total apparent power, each phase and average power factor (positive and negative),
accumulated energy, earth current, unbalanced current and user A and user B accumulated energy.
NOTE:
Power factor shows as following,
Remark:
P stands for active power
Q stands for reactive power
Table 6 Power Factor Description
⚫
Bus
, including as below,
Phase voltage, line voltage, frequency, phase sequence.
⚫
SNYC
, including as below,
Synchronoscope
,
power percentage, and MSC status.
⚫
Alarm
Display all alarm information, including warn, shutdown alarm, trip shutdown and trip but not shutdown.
NOTE:
For ECU alarms and shutdown alarms, if the alarm information is displayed, check engine according to it,
otherwise, please check the generator manual according to SPN alarm code.
⚫
Event log
Make records about all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or
stop) and the real time when alarm occurs and genset parameters.
⚫
Others
, including,
Time and Date, maintenance due, input/output ports status, network settings and etc.
⚫
About,
including,
Issue time of software and hardware version, product PD number.
Power factor Conditions Active power Reactive power
Remark
COS>0L
P>0, Q>0
Input
Input
Load is inductive resistance.
COS>0C
P>0, Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0, Q>0
Output
Input
Load is equal to one under excitation
generator.
COS<0C
P<0, Q<0
Output
Output
Load is equal to one over excitation
generator.
Remark:
1.
Input active power, generator sends active power to load.
2.
Output active power, load supplies electricity to generator.
3.
Input reactive power, generator sends reactive power to load.
4.
Output reactive power, load sends reactive power to generator.