HGM8151 Genset Parallel Controller User Manual Page 33 of 66
No.
Items
Parameters
Defaults
Description
pre-set balanced running time.
21 Fail to Sync Delay
(5.0-300.0)s
60.0
When the controller detects no Sync signal
during the preset delay, it will send
corresponding alarm signal according to
the action type.
Action Type:
0: Warn; 1: Trip.
22 Fail to Sync Action
(0-1)
0
23 NEL Trip Enable
(0-1)
0
0: Disable 1: Enable;
Details of function description please see
the following.
24 NEL Trip Value 1
(0-200)%
90%
25 NEL Trip Delay 1
(0-3600)s
5
26 NEL Trip Value 2
(0-200)%
100%
27 NEL Trip Delay 2
(0-3600)s
1
28
NEL Auto Reconnect
Enable
(0-1)
0
29
NEL Auto Reconnect
Value
(0-200)%
50%
30
NEL Auto Reconnect
Delay
(0-3600)s
5
31 NEL Number
(1-3)
3
Sync Setting - GOV
1
Output Type
(0-1)
1
0: Relay output; 1: Analog Voltage Output
2
Output Reverse
(0-1)
0
0: Disable; 1: Enable.
3
Loading Action
(0-2)
1
0: None; 1: Adjust to Rated Frequency; 2:
Adjust to Center Point
4
Center Voltage SW1 (0-10.0)
0
Default central voltage: 0V.
5
Voltage Range SW2
(0-10.0)
2.0
Default volt. range: (-1.5~+1.5)V.
6
Sync Gain
(0-500)
20
Adjust and control before paralleling.
7
Sync Stability
(0-2000)
20
Adjust and control before paralleling.
8
Load Control Gain
(0-500)
20
Adjust and control after paralleling.
9
Load
Control
Stability
(0-2000)
20
Adjust and control after paralleling.
Sync Setting - AVR
1
Output Type
(0-1)
1
0: Relay output; 1: Analog Voltage Output
2
Output Reverse
(0-1)
0
0: Disable; 1: Enable.
3
Loading Action
(0-2)
1
0: None; 1: Adjust to Rated Frequency; 2:
Adjust to Center Point
4
Centre Voltage SW1 (0-10.0)
0
Default central voltage: 0V.
5
Voltage Range SW2
(0-10.0)
2.0
Default volt. range: (-1.5~+1.5)V.
6
Sync Control Gain
(0-500)
20
Adjust and control before paralleling.
7
Sync
Control
Stability
(0-2000)
20
Adjust and control before paralleling.
8
Load Control Gain
(0-500)
20
Adjust and control after paralleling.