Installation
Service Manual
SKOPE OD400
‐
2
5
Installation
Climate Class
The chiller is designed to operate within a climate class 3 environment (25°C
@ 60% RH). We recommend that you put the chiller in the coolest place
possible because it will use less power and last longer.
Chiller
Location
The location of the chiller may be the single most important decision that will
extend its life and ensure economical, high performance. Ensure the cabinet
sits on a level surface to prevent the condensate tray from overflowing.
Air Movement
The cabinet must
NOT
be situated where it is affected by air-conditioning air
outlets, ventilation fans or air re-circulation fans, as this will compromise the
airflow and thus product temperature in the open cabinet zone.
There must be
NO
air movement directly into the cabinet opening. Air
movement will cause failure of the air curtain over the product, resulting in
excessive temperature rise. Detectable air draft will adversely effect the
cabinet operation. Maximum air movement across the cabinet opening must
not exceed 0.2 m/s.
Power Cord
The chiller has a flexible power cord fitted with a 3-pin plug, which exits the
rear of the cabinet at floor level. Locate the power cord before the cabinet is
moved into position so that it is not trapped behind the cabinet.
Ventilation
Adequate ventilation must be provided around the refrigeration unit and
cabinet at all times. Refrigeration exhaust air must not be restricted, and
must be able to easily flow out and away from the cabinet.
Ensure there is unimpeded clearance in front of the front panel at all times.
Never store cardboard cartons or other items in the front or rear of the
refrigeration unit.
Determine if the installation is free-standing or enclosed, and ensure the
installation meets the ventilation requirements detailed below.
Free-standing installations
Free-standing cabinets must be installed with the following minimum
clearances (also see diagrams over page):
30mm behind (provided by the rear spacers on the back of the cabinet).
60mm on either side of the cabinet.
500mm above the cabinet.
If these clearances can’t be met, the installation should be treated as an
enclosed installation.
IMPORTANT
There must be
NO
air movement directly into the cabinet
opening.
CAUTION
Ensure adequate ventilation clearance around the refrigeration
unit and cabinet.