14
Electronic Controller
Service Manual
SKOPE OD400
‐
2
Field Adjustable Programming
Within each program set are field adjustable (Type C) parameters. To assist
with locating, the parameters can be displayed in groups detailed in the table
below. Non-useful parameters are hidden.
Parameter groups
Changes to SKOPE factory default programs are not recommended.
To access Type C parameters
To modify ‘Type C’ parameters
Display Icon
Group
Display Icon
Group
Pro
Probe
Fan
Fan
Ctl
Temperature
CnF
General
CMP
Compressor
HcP
HACCP
dEF
Defrost
rtc
Real time clock
ALM
Alarm
1. Press the
key and
keys
together for more than 5 seconds.
The display will show either ‘
00
’ or ‘
-
1
’, representing the password
prompt.
2. Press the
or
keys until
displaying the password number ‘
66
’
3. Confirm by pressing the
key. The
display will show the code of the first
modifiable ‘Type C’ parameter.
1. Press the
or
keys until
reaching the parameter to be modified.
When scrolling, an icon appears on the
display representing the category the
parameter belongs to.
2. Alternatively, press the
key to
display a menu that is used to quickly
access the group of parameters to be
modified (see table on previous page).
Continued over page