2.6
Malfunction display: Indoor unit water full protection
Water full protection
Is the water overflow?
Is the
water drainage pipe jammed or
water flows smoothly?
Check the
water drainage pump:
is it works?
Replace the mainboard of the
indoor unit
Adjust the water drainage pipe
Yes
No
Yes
Maintain the cables of water
drainage pump
Clear the water drainage pipe
Yes
Yes
No
No
Check the
Voltage of liquid level
switch : is it ok?
Maintain the liquid level
switch
Check the
Voltage of water drainage
pump : is it ok?
Replace the mainboard of the
indoor unit
Yes
Yes
No
No
2.7
Malfunction display: Temperature sensor error
The resistance value of discharge temperature sensor is 50 K
Ω
;
The resistance value of outside temperature sensor and inside temperature sensor are all 15 K
Ω
;
The others are 20 K
Ω
.
Temperature sensor error
The plug
on temperature sensor is correctly
connected to the socket on
mainboard, is it?
Remove the
temperature and measure its
resistance value: is it within
normal range?
Replace the mainboard of unit
Check the orientation of
plug and socket
Replace the temperature
sensor
Yes
No
Yes
No
69
Summary of Contents for MS-E48AIN
Page 1: ...HIGH POWER MULTI SYSTEM SERVICE MANUAL EN MS E48AIN MS E56AIN Outdoor unit ...
Page 11: ...CONTROL 1 OPERATION FLOWCHART 6 ...
Page 13: ...1 2 Heating Operation 8 ...
Page 47: ... Outdoor unit higher than indoor unit DB DB DB DB 42 ...
Page 70: ...Malfunction display High Pressure Protection 2 1 65 ...
Page 87: ...PARTS GUIDE MS E48AIN MS E56AIN DB2 19SB DB3 19SB DB5 16AF HIGH POWER MULTI SYSTEM ...
Page 88: ...Exploded view of unitMS E48AIN ...
Page 91: ...Exploded view of unitMS E56AIN ...
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......