5.1
Allowable Length and Drop Height of Connecting Pipe
The sorts
The pipes
Length
(
m
)
Maximum
allowable
length
L1+L2+L3+L4+L5
≤
55
unit and DB
Total length between outdoor unit and DB
Total length
between indoor
1A+1B+1C+2A+2B+2C+
3A+3B
≤
80
modules
MS-E48AIN
MS-E56AIN
≤
90
Between indoor unit and DB module
1A;1B;1C;2A;2B;2C;3A;3B
≤
15
L4+1B;L2+L5+2A;
L2+L3+3B
≤
40
Maximum
allowable
length
H1
≤
30
H2
≤
30
H3
≤
15
Between indoor unit and the 1st branch
Between outdoor and indoor units
Between outdoor units and DB
Between DB and DB modules
Between indoor and indoor units
H4
≤
15
Minimum
allowable
length
≥
5
Between outdoor and the 1st branch
L1
Between DB and the branch
L3;L4;L5
as possible
as short
DB module should be placed within the level between the outdoor unit and indoor unit.
5.2
Dimension of Connecting Pipe
Outdoor unit
Sorts
Gas Pipe
(
mm
)
Liquid Pipe
(
mm
)
MS-E48AIN
Φ
15.9
Φ
9.52
MS-E56AIN
Φ
19.05
Between outdoor unit and the 1st branch
The pipe L1
Φ
19.05
Φ
9.52
Φ
9.52
Between the 1st and the 2nd branch
The pipe L2
Φ
15.9
5.3
Connection of Branch Pipe
1)
If two or three DB modules used, Y-type branch pipe of MS-01B will be chosen.
REFRIGERATION PIPING WORK
5
DB
DB
DB
40
Summary of Contents for MS-E48AIN
Page 1: ...HIGH POWER MULTI SYSTEM SERVICE MANUAL EN MS E48AIN MS E56AIN Outdoor unit ...
Page 11: ...CONTROL 1 OPERATION FLOWCHART 6 ...
Page 13: ...1 2 Heating Operation 8 ...
Page 47: ... Outdoor unit higher than indoor unit DB DB DB DB 42 ...
Page 70: ...Malfunction display High Pressure Protection 2 1 65 ...
Page 87: ...PARTS GUIDE MS E48AIN MS E56AIN DB2 19SB DB3 19SB DB5 16AF HIGH POWER MULTI SYSTEM ...
Page 88: ...Exploded view of unitMS E48AIN ...
Page 91: ...Exploded view of unitMS E56AIN ...
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......