acceptable if pressure drop is within 0.02MPa. (With the
temperature change by 1
, the pressure will change by
℃
approx. 0.01MPa)
Thermal insulation
◆
The thermal insulation tube must meet the specifications.
◆
Seal between the thermal insulation pipes to avoid air entry.
Installation of outdoor unit
◆
Select the installing position correctly.
◆
Build the foundation according to the anchor bolt position and
the dimension of outdoor unit
◆
Build the damping device properly.
◆
Avoid sharp knock when handling the outdoor unit. The
inclination angle shall not be higher than 15°.
Connection of indoor unit and outdoor unit
◆
Tighten the nuts.
◆
Provide proper protection to the outdoor connection pipe,
communication wires and power supply.
Leakage detection under pressure
◆
Keep the pressure for 24 hours. Except for the influence by
temperature, it is deemed acceptable if pressure drop is within
0.02MPa. (With the temperature change by 1
℃
, the pressure
will change by approx. 0.01MPa).
Vacuuming
◆
Establish vacuum simultaneously in the gas pipe and liquid
pipe;
◆
The vacuuming time shall be long enough.
◆
Put still for 1 hour after vacuuming. It is deemed acceptable if
the pressure will not rise.
Add refrigerant
◆
Add refrigerant according to the volume as specified on the
engineering drawing.
Open the valve of outdoor unit
Commissioning of complete unit
Remarks:
a. Described above are general working procedures. The procedures might vary with the site conditions.
b. For detailed installation rules, please see the description in each chapter
30
Summary of Contents for MS-E48AIN
Page 1: ...HIGH POWER MULTI SYSTEM SERVICE MANUAL EN MS E48AIN MS E56AIN Outdoor unit ...
Page 11: ...CONTROL 1 OPERATION FLOWCHART 6 ...
Page 13: ...1 2 Heating Operation 8 ...
Page 47: ... Outdoor unit higher than indoor unit DB DB DB DB 42 ...
Page 70: ...Malfunction display High Pressure Protection 2 1 65 ...
Page 87: ...PARTS GUIDE MS E48AIN MS E56AIN DB2 19SB DB3 19SB DB5 16AF HIGH POWER MULTI SYSTEM ...
Page 88: ...Exploded view of unitMS E48AIN ...
Page 91: ...Exploded view of unitMS E56AIN ...
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......